484 Greenwich St. Building and Mechanical f= Inspection eal i is ial dil i i ee insti ‘eG 44 — EFTA00505930

--=PAGE_BREAK=--

Front of building showing brick pointing maintenance needed. EFTA00505931

--=PAGE_BREAK=--

Exterior Brick — front facade of building needs brick pointing maintenance EFTA00505932

--=PAGE_BREAK=--

Newly constructed building adjacent to 484 Greenwich — void between buildings needs to be covered from exterior EFTA00505933

--=PAGE_BREAK=--

Fire and Water service — exterior covering discolored, needs to be repainted. EFTA00505934

--=PAGE_BREAK=--

Street hatch door — needs to be replaced at street level to water tight hatch to avoid future basement flooding EFTA00505935

--=PAGE_BREAK=--

Main incoming electric from Con Edison still left open. Main electric supply lines and box replaced. As you can see by the discoloration on the brick walls and 100% saturated moisture readings on the brick that water sat in the basement for a long period of time and destroyed the original electrical service EFTA00505936

--=PAGE_BREAK=--

New three phase service junction box installed, left open by electrician, replaced after Hurricane Sandy EFTA00505937

--=PAGE_BREAK=--

New electrical equipment breaker panel installed and left open by electrician. Check to see if the owner had new panels inspected by NYC EFTA00505938

--=PAGE_BREAK=--

Rusted door in basement showing water level form standing water from flood. EFTA00505939

--=PAGE_BREAK=--

Basement ceiling — remove from water damage, water entered street hatch above exit door and destroyed ceiling EFTA00505940

--=PAGE_BREAK=--

Masonry crack in basement foundation wall on Greenwich street side, needs to be checked by structural engineer to see how deep the crack extends outward EFTA00505941

--=PAGE_BREAK=--

Large Masonry crack in basement wall was previously repaired with hydraulic cement, should be checked by structural engineer EFTA00505942

--=PAGE_BREAK=--

Main Stair well wall brick patching, possible water seepage EFTA00505943

--=PAGE_BREAK=--

Rusted stair steel shows water in basement for a long period of time. Super storm Sandy hit October 29", many basements on Greenwich St. did not get pumped out until November 11". EFTA00505944

--=PAGE_BREAK=--

Basement at building next to 484 Greenwich pumped out on 11/08/12 EFTA00505945

--=PAGE_BREAK=--

New Trane XR80 boilers installed after hurricane Sandy, air conditioning coil not hooked up to condenser unit on roof. No air conditioning on the lower three floors of the residence EFTA00505946

--=PAGE_BREAK=--

Trane Heating /AC unit in basement cooling coil for ac not connected to condenser unit on roof no ac on floors,1,2&3 EFTA00505947

--=PAGE_BREAK=--

Trane RX80 units picture shows no ac/coils hooked up for Air Conditoning EFTA00505948

--=PAGE_BREAK=--

New Gas Hot Water Heater A/O Smith EFTA00505949

--=PAGE_BREAK=--

Gas & Fire sprinkler Service — looks in good condition EFTA00505950

--=PAGE_BREAK=--

Elevator Control panel — looks newly installed, elevator in process of being rebuilt. No elevator service in house at this time ( ((A\\ ee EFTA00505951

--=PAGE_BREAK=--

Hydraulic elevator not in operation — water in hydraulic oil, this part of the elevator will possibly be replaced or drained and repaired. EFTA00505952

--=PAGE_BREAK=--

Main Water service and Fire service in good condition EFTA00505953

--=PAGE_BREAK=--

Fire Dry Pipe sprinkler system in good condition. EFTA00505954

--=PAGE_BREAK=--

Fire dry pipe in good operating order EFTA00505955

--=PAGE_BREAK=--

Lobby floor crack damage EFTA00505956

--=PAGE_BREAK=--

Entrance lobby floor crack damage EFTA00505957

--=PAGE_BREAK=--

Lobby floor Cracked in many areas EFTA00505958

--=PAGE_BREAK=--

Lobby Floor cracks EFTA00505959

--=PAGE_BREAK=--

Main steel support for warehouse Industrial strength column and beam EFTA00505960

--=PAGE_BREAK=--

Office floor Wood floor worn from office chairs. EFTA00505961

--=PAGE_BREAK=--

Front Door security intercom operational /Central music system EFTA00505962

--=PAGE_BREAK=--

Exposed air duct system EFTA00505963

--=PAGE_BREAK=--

Windows operational but out dated EFTA00505964

--=PAGE_BREAK=--

Side Window blocked by new building and large masonry crack in wall EFTA00505965

--=PAGE_BREAK=--

Wood floor damage laundry room, floor lifted from water damage. EFTA00505966

--=PAGE_BREAK=--

Kitchen appliances original to 1999 renovation EFTA00505967

--=PAGE_BREAK=--

Terrace Blocked by new building wall EFTA00505968

--=PAGE_BREAK=--

Brick in main stair roof level shows signs of water seepage EFTA00505969

--=PAGE_BREAK=--

Wood decking on roof - original needs replacement due to rotting. aS EFTA00505970

--=PAGE_BREAK=--

New Trane Condenser units installed above upper front terrace above out door shower mechanical noise over head of main roof terrace. EFTA00505971

--=PAGE_BREAK=--

Bedroom AC unit also above roof terrace concealed in wood enclosure. ‘qa EFTA00505972

--=PAGE_BREAK=--

Kitchen floor key pad area for ac/system alarm system inter com central music system EFTA00505973

--=PAGE_BREAK=--

Wood roof deck rotted wood and tripping hazzard.Deck needs to be replaced. EFTA00505974

--=PAGE_BREAK=--

Mechanical Equipment enclosure above roof deck check noise level when all equipment is running .Access for maintenance and installations limited. EFTA00505975